Accuracy: ±0.25%, ±0.40% or ±0.60% of span
Differential Pressure Ranges:
Unidirectional: 0.10 in.W.C. to 100.00 in.W.C.
Bidirectional: ±0.10 in.W.C. to ±50.00 in.W.C.
NEMA 1; ABS enclosure
Mounting: surface mount
Output signal: current or voltage
The core component of the Model 164series differential pressure
sensor/transmitter is a capacitive pressure sensor, which consists of a
stainless steel diaphragm with a fixed electrode forming a capacitor
whose value varies with pressure. Using the company's special patented
technology carefully designed sensor sensors and unique detection
circuit to ensure good temperature performance and long-term stability
of the product.
The
Model 164 differential pressure sensor/transmitter can be used to
measure differential or gauge pressure with outputs of 0-5V, 0-10V,
4-20mA, and can also be customized for other outputs. The accuracy of
Model 164 was ±1.0%FS, 0.4%FS or 0.25%FS at room temperature. The
temperature compensation ranges from 4 ℃ to 77℃, and the temperature
effect is less than ±0.05%FS/℃.
Model
164 has excellent performance-price ratio, widely used in HVAC,
environmental pollution control, clean engineering, medical instruments
and equipment, oven pressurization and furnace pressure control, natural
gas, gas pipe network monitoring, underground ventilation and power
plant wind pressure monitoring and other fields.
The positive/negative pressure end can withstand at least 100kPa overload without damage
With temperature compensation capacitive sensitive element, to ensure the transmitter excellent movement State/static temperature performance
Multiple pressure interfaces/output forms/installation modes are optional
True zero output of voltage
Asymmetrical bidirectional differential pressure range is optional
Full protection of misconnection
Meet the CE standard
Environmental protection design, in line with ROHS standards
Minimum pressure range of 10Pa
Parameter | Standard | Special selection | Special selection |
Accuracy RSS*(under constant temperature) | ±1.0%FS | ±0.40%FS | ±0.25%FS |
nonlinearity(best fitting line) | ±0.97%FS | ±0.37%FS | ±0.24%FS |
lag | ±0.20%FS | ±0.10%FS | ±0.05%FS |
non-repeatability | ±0.10%FS | ±0.10%FS | ±0.05%FS |
Temperature effect | |||
Zero point/Full range offset(/℃) | ±0.05%FS | ±0.03%FS | ±0.02%FS |
Compensation range | 4℃ to 77℃ | ||
Maximum static pressure | 15PSI(100kPa) | ||
Overload | Both positive and negative are 15PSI(100kPa) | ||
Stability ratio | ±0.5% FS/YR | ||
Preheat | 5 seconds to reach the performance specification | ||
Installation position effect | When factory calibration, the sensor is placed vertically. In order to ensure accuracy, necessary fine tuning should be made when installing other positions at zero point |
Environmental and mechanical parameters | |
Operating temperature | -18℃ to 77℃ |
Storage temperature | -40℃ to 85℃ |
Electrical connection | Wiring terminal |
Pressure connection | 3/16"、φ8、φ6.5 brass tower pressure connection(optional) |
Output regulation | remove the terminal cover to fine-tune zero/full range |
Pressure medium | Air or other non-conductive gas |
Shell | Stainless steel/PC+ABSalloy,94V-0 |
Weight | 165g |
Installation | Refer to the product specification for outline dimensions as shown in Figure 1 |